Parameter Descriptions
12-49
Enables/disables the function which allows the drive to start into a 
spinning motor at actual RPM when a start command is issued.
Normally, when a drive is started in its normal mode, it initially 
applies a frequency of 0 Hz and ramps to the desired frequency. If 
the drive is started into an already spinning motor in this manner 
without Flying Start enabled, large currents will be generated and 
an overcurrent trip may result. 
In Flying Start mode, the drive's response to a start command will 
be to identify the motor's speed and apply a voltage that is 
synchronized in frequency, amplitude and phase to the counter emf 
of the spinning motor. The motor will then accelerate to the desired 
frequency.
Adjusts the responsiveness of the flying start function. Increasing 
the value in this parameter increases the responsiveness of the 
flying start function.
169
Flying Start En
Range:
0 = Disabled
1 = Enabled
Default:
0 = Disabled
Access:
2
Path: Dynamic Control>Stop/Restart Modes
See also:
170
170
Flying StartGain
Range:
20 to 32767 [1]
Default:
4000
Access:
2
Path: Dynamic Control>Stop/Restart Modes
See also:
169