Parameter Descriptions

12-35

Sets the lower limit of the process PI output. This value must be less
than the value set in PI Upper Limit (132).

Sets the upper limit of the process PI output. This value must be
greater than the value set in PI Lower Limit (131).

Sets the value used to load into the PI Integrator while the PI
regulator is disabled. This allows better dynamic starting
performance at the time the regulator is enabled. Refer to figure
12.16.

131

PI Lower Limit

Range:

-/+400.0 Hz

Default:

-Maximum Freq

Access:

2

Path: Speed Command>Process PI

See also:

124-138

132

PI Upper Limit

Range:

-/+400.0 Hz [0.1 Hz]

Default:

+Maximum Freq

Access:

2

Path: Speed Command>Process PI

See also:

124-138

133

PI Preload

Range:

-/+400.0 Hz [0.1 Hz]

Default:

0.0 Hz

Access:

2

Path: Speed Command>Process PI

See also:

124-138

Figure 12.16 – PI Preload Value

Preload Value

Spd

Cmd

PI_Config

PreLoadCmd

PI_Status

Enabled

PI

Integrator

(124)

(134)

(133)