Parameter Descriptions
12-33
Selects the source of the outer control loop process PI reference
signal.
Provides an internal register value for the process setpoint when PI
Reference Sel (126) is set to PI Setpoint.
126
PI Reference Sel
Range:
0 = PI Setpoint (127)
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Master Ref
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = Reserved
22 = Network
23 = Reserved
Default:
0 = PI Setpoint (127)
Access:
2
Path: Speed Command>Process PI
See also:
124-138
127
PI Setpoint
Range:
-/+100.00% of Maximum Process Value [0.01%]
Default:
50.00%
Access:
2
Path: Speed Command>Process PI
See also:
124-138