12-38

SP600 AC Drive User Manual

Sets the rate of deceleration for all speed decreases.

Max Speed / Decel Time = Decel Rate

Two decel times exist to enable deceleration rate changes “on the
fly” using a network command, digital input, or F-Key on the LCD
OIM, if configured (see chapter 9 for information on configuring
F-Keys).

Sets the percentage of acceleration or deceleration time that is
applied to the ramp as an S curve. Time is entered as a percentage
of accel or decel time, and ramp times are extended, 1/2 at the
beginning and 1/2 at the end of the ramp.

For example: Accel = 10 sec
S-Curve % = 25%

2.5 seconds will be added to the accel time, 1.25 seconds of
rounding at each end of the ramp.

Selects the source for the adjustment of current limit (i.e.,
parameter, analog input, etc.). Allows for external current limit via
analog inputs.

If an analog input is selected (1, 2), Analog In

x

Lo = 0% limit,

Analog In

x

Hi = 150% limit.

142
143

Decel Time 1
Decel Time 2

Range:

0.1 to 3600.0 Sec [0.1 Sec]

Default:

10.0 Sec

Access:

142=0
143=2

Path: Dynamic Control>Ramp Rates

See also:

142, 143, 146, 361-366

146

S Curve %

Range:

0 to 100% [1%]

Default:

0%

Access:

0

Path: Dynamic Control>Ramp Rates

See also:

140 - 143

147

Current Lmt Sel

Range:

0 = Curr Lim Val
1 = Analog In 1
2 = Analog In 2

Default:

0 = Cur Lim Val

Access:

2

Path: Dynamic Control>Load Limits

See also:

148, 149