Parameter Descriptions

12-25

Analog input reference scaling. Scales the lower value of the Speed
Ref A Sel (90) selection when the source is an analog input.

Important:

Parameter 92 corresponds to Analog In 1 Lo (323) or
Analog In 2 Lo (326) depending on the analog input
assigned as a source. See figure 12.51.

Specifies the manual speed reference source when a digital input is
configured for manual mode selection. See parameters 361-366.

Analog input reference scaling. Scales the upper value of the TB
Man Ref Sel (96) selection when the source is an analog input.
Parameter 97 should be set in conjunction with Analog In 1 Hi (322)
or Analog In 2 Hi (325) depending on the appropriate analog input
used. See figure 12.51.

92

Speed Ref A Lo

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

1

Path: Speed Command>Speed References

See also:

81

96

TB Man Ref Sel

Range:

1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7

Default:

2 = Analog In 2

Access:

1

Path: Speed Command>Speed References

See also:

97, 98, 361-366

97

TB Man Ref Hi

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

Maximum Speed

Access:

1

Path: Speed Command>Speed References

See also:

96