Parameter Descriptions

12-81

The drive scales the value read from the analog input and converts
it to scaled units for the drive. The user controls the scaling by
setting parameters that associate a low and high point in the input
range with a low and high point in the target range.

Analog In 1 Hi sets the highest input value to the analog input 1
scaling block. See figure 12.51.

322

Analog In 1 Hi

Range:

4.000 to 20.000 mA [0.001 mA]
+/-10.000 VDC [0.001 V]
0.000 to 10.000 V [0.001 V]

Default:

20.000 mA

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92, 320

Analog Input Scaling Example

Assume:

• Speed Ref A Sel = Analog In 1

• Ref Lo (92) = 10 Hz

• Ref Hi (91) = 60 Hz

• Analog In 1 Lo (323) = 0.0 V

• Analog In 1 Hi (322) = 10.0 V

• Analog In Config (320) = xxxx...xx00

Figure 12.51 – Analog Input Scaling Example

0

10 V

V

in

Analog In Hi

(322)

Analog In Lo

(323)

Ref Lo

(92)

10 Hz

Ref Hi

(91)

60 Hz