Table 4.5 – SP600 208/240 VAC Input Recommended Protection Devices

Model

Number

HP

Dual Element

Time Delay

Fuse

Non-time

Delay Fuse

Circuit

Breaker

1

ND

HD

Min

2

Max

3

Min

2

Max

3

Max

4

208 VAC Input

6SP201-2P2

0.5

0.33

6

6

6

10

15

6SP201-4P2

1

0.75

10

10

10

17.5

15

6SP201-6P8

2

1.5

15

15

15

30

30

6SP201-9P6

3

2

20

25

20

40

40

6SP201-015

5

3

20

35

20

70

70

6SP201-022

7.5

5

25

50

25

100

100

6SP201-028

10

7.5

35

70

35

125

125

6SP201-042

15

10

60

100

60

175

175

6SP201-054

20

15

80

125

80

200

200

6SP201-070

25

20

90

175

90

300

300

240 VAC Input

6SP201-2P2

0.5

0.33

4

4.5

6

8

15

6SP201-4P2

1

0.75

6

9

10

15

15

6SP201-6P8

2

1.5

15

15

15

25

25

6SP201-9P6

3

2

20

20

20

35

35

6SP201-015

5

3

20

30

20

60

60

6SP201-022

7.5

5

25

45

25

80

80

6SP201-028

10

7.5

35

60

35

110

110

6SP201-042

15

10

50

90

50

150

150

6SP201-054

20

15

60

100

60

200

200

6SP201-070

25

20

90

150

90

275

275

1

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum

2

Minimum protection device size is the lowest rated device that supplies maximum
protection without nuisance tripping.

3

Maximum protection device size is the highest rated device that supplies drive protection.
For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

4

Maximum allowable by US NEC. Exact size must be chosen for each installation.