Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 265
 
Technical Specifications
A-5
Electronic Motor 
Overload
Protection
Class 10 protection with speed-sensitive 
response. Investigated by U.L. to comply with 
N.E.C. Article 430. U.L. File E59272, volume 12.
Table A.5 – Control (Continued)
Table A.6 – Control Inputs, Outputs, and Power Supplies
Analog Input 1, 
Differential Voltage Input
 Signal level
 Differential Input resistance
 Isolation
 Initial accuracy (@25°C)
 Resolution
 Input processing period
 Terminal block size
 
 Protection
0 to +10V
60k
Ω
±17V
±0.3%
10 bits (0.1%)
5ms
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
ESD protected (6 kV contact 
discharge, 8 kV air discharge)
Analog Input 1, 
Differential Current Input
 Signal level
 Differential Input resistance
 Isolation
 Initial accuracy (@25°C)
 Resolution
 Input processing period
 Terminal block size
 
 Protection
0(4) to 20mA
100
Ω
±9V
±0.3%
10 bits (0.1%)
5ms
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
ESD protected (6 kV contact 
discharge, 8 kV air discharge)
Analog Input 2, 
Differential Voltage Input
 Signal level
 Differential Input resistance
 Isolation
 Initial accuracy (@25°C)
 Resolution
 Common Mode Rejection Ratio
 Input processing period
 Terminal block size
Protection
-10V to +10V
88k
Ω
±165V
±0.3%
10 bits (0.1%)
70dB up to 500Hz over temperature 
range
5ms
0.05 mm
2
to 1.5 mm
2
(30 AWG to
16 AWG) 
ESD protected (6 kV contact 
discharge, 8 kV air discharge)