Technical Specifications

A-5

Electronic Motor
Overload
Protection

Class 10 protection with speed-sensitive
response. Investigated by U.L. to comply with
N.E.C. Article 430. U.L. File E59272, volume 12.

Table A.5 – Control (Continued)

Table A.6 – Control Inputs, Outputs, and Power Supplies

Analog Input 1,
Differential Voltage Input
Signal level
Differential Input resistance
Isolation
Initial accuracy (@25°C)
Resolution
Input processing period
Terminal block size

Protection

0 to +10V
60k

±17V
±0.3%
10 bits (0.1%)
5ms
0.05 mm

2

to 1.5 mm

2

(30 AWG to

16 AWG)
ESD protected (6 kV contact
discharge, 8 kV air discharge)

Analog Input 1,
Differential Current Input
Signal level
Differential Input resistance
Isolation
Initial accuracy (@25°C)
Resolution
Input processing period
Terminal block size

Protection

0(4) to 20mA
100

±9V
±0.3%
10 bits (0.1%)
5ms
0.05 mm

2

to 1.5 mm

2

(30 AWG to

16 AWG)
ESD protected (6 kV contact
discharge, 8 kV air discharge)

Analog Input 2,
Differential Voltage Input
Signal level
Differential Input resistance
Isolation
Initial accuracy (@25°C)
Resolution
Common Mode Rejection Ratio

Input processing period
Terminal block size

Protection

-10V to +10V
88k

±165V
±0.3%
10 bits (0.1%)
70dB up to 500Hz over temperature
range
5ms
0.05 mm

2

to 1.5 mm

2

(30 AWG to

16 AWG)
ESD protected (6 kV contact
discharge, 8 kV air discharge)