12-100

SP600 AC Drive User Manual

24 = Input 4 Link: Outputs the state of digital input 4.

25 = Input 5 Link: Outputs the state of digital input 5.

26 = Input 6 Link: Outputs the state of digital input 6.

27 = TB in Manual: Terminal block has manual reference control.

Sets the relay activation level for options 10-15 in parameter 384
(Digital Out2 Sel). Units are assumed to match the selection in
parameter 384 (i.e., At Freq = Hz, At Torque = Amps).

Sets the on delay time for the digital outputs. This is the time
between the occurrence of a condition and activation of the relay.

385

Dig Out2 Level

Range:

0.0 to 819.2 [0.1]

Default:

0.0

Access:

1

Path: Inputs & Output>Digital Outputs

See also:

384

386

Dig Out2 OnTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Output>Digital Outputs

See also:

384