When using the braking resistor connections, parameter 163 (DB 
Resistor Type) must be set to one of the following selections:
•
0 = Internal: Refers to DB plate-style resistor options kits that can 
be mounted directly to the heatsink chassis of the drive (for 
example, 6SP2-DB1-A).
•
1 = External: Refers to externally-mounted resistors. These 
could be panel, cage, or other type of mounting, and are not 
specifically designed by Rockwell Automation to mount directly to 
the SP600 AC drive.
!
ATTENTION: AC drives do not offer protection for 
externally mounted braking resistors. A risk of fire 
exists if external braking resistors are not protected. 
External resistor packages must be self-protected 
from overtemperature, or the protective circuit 
shown in figure 6.8, or an equivalent, must be 
supplied.
ATTENTION: Equipment damage may result if a 
drive-mounted (internal) resistor is installed and 
parameter 163 is set to 1 (External Res). Thermal 
protection for the internal resistor will be disabled, 
resulting in possible device damage
Figure 6.8 – Protective Circuit for External Resistor Packages
Power On
R (L1)
S (L2)
T (L3)
Power Source
DB Resistor Thermostat
Power Off
M
M
(Input Contactor) M
Three-Phase
AC Input
AC Drive