Technical Specifications

A-1

A

PPENDIX

A

Technical Specifications

Table A.1 – Protection

208V

Drive

240V

Drive

400V

Drive

480V

Drive

575V

Drive

AC Input Overvoltage Trip

247 VAC 285 VAC 475 VAC 570 VAC 690 VAC

AC Input Undervoltage Trip

120 VAC 138 VAC 233 VAC 280 VAC 345 VAC

Bus Overvoltage Trip

350 VDC 405 VDC 675 VDC 810 VDC 1013 VDC

Bus Undervoltage Trip

160 VDC 160 VDC 300 VDC 300 VDC 375 VDC

Nominal Bus Voltage

281 VDC 324 VDC 540 VDC 648 VDC 810 VDC

All Drives

Heat Sink Thermistor

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Current Limit
Hardware Current Limit
Instantaneous Current Limit

20 to160% of rated current
200% of rated current (typical)
220-300% of rated current (dependent on
drive rating)

Line transients

Up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity Showering arc transients up to 1500 V peak

Power Ride-Thru

15 milliseconds at full load

Logic Control Ride-Thru

0.5 seconds minimum, 2 seconds typical

Ground Fault Trip

Phase-to-ground on drive output

Short Circuit Trip

Phase-to-phase on drive output