1 power wire sizes – Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 57

Advertising
background image

Wiring Requirements for the Drive

4-3

4.1.1 Power Wire Sizes

Input power wiring should be sized according to applicable codes to
handle the drive’s continuous-rated input current. Output wiring
should be sized according to applicable codes to handle the drive’s
continuous-rated output current. See table 4.2 for the range of
power wire sizes that the terminals can accommodate.

Table 4.1 – Recommended Shielded Wire

Location

Rating/Type

Description

Standard
(Option 1)

600V, 90°C (194°F)
XHHW2/RHW-2
Anixter
B209500-B209507,
Belden 29501-29507,
or equivalent

• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and

tinned copper drain wire.

• PVC jacket.

Standard
(Option 2)

Tray rated 600V, 90° C
(194° F) RHH/RHW-2
Anixter OLF-7xxxxx or
equivalent

• Three tinned copper conductors with XLPE

insulation.

• 5 mil single helical copper tape (25% overlap min.)

with three bare copper grounds in contact with
shield.

• PVC jacket.

Class I & II;
Division I & II

Tray rated 600V, 90° C
(194° F) RHH/RHW-2
Anixter 7V-7xxxx-3G
or equivalent

• Three bare copper conductors with XLPE insulation

and impervious corrugated continuously welded
aluminum armor.

• Black sunlight-resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.

Table 4.2 – Power Terminal Block Specifications

Name

Description

Frame

Wire Size Range

1

1

Maximum/minimum sizes that the terminal block will accept. These are
not recommendations.

Torque

Max

Min

Power
Terminal Block

Input power
and motor
connections

A, B & C 3.5 mm

2

(12 AWG)

0.3 mm

2

(22 AWG)

0.6 N-m

(5 in-lb)

D

8.4 mm

2

(8 AWG)

0.8 mm

2

(18 AWG)

1.4 N-m

(12 in-lb)

E

25.0 mm

2

3 AWG)

2.5 mm

2

(14 AWG)

2.71 N-m

(24 in-lb)

SHLD
Terminal

Terminating
point for
wiring shields

All

---

---

1.6 N-m

(14 in-lb)