Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 24
 
2-10
SP600 AC Drive User Manual
Refer to the descriptions of parameters 174 and 175 in chapter 12 
for more information about using the Auto Restart feature.
2.4.11 Autotune
The Autotune feature, enabled in parameter 61 (Autotune), 
identifies the motor flux current and stator resistance for use in 
Sensorless Vector Control and Economizer modes (selected in 
parameter 53). The result of the flux current test procedure is stored 
in the Flux Current parameter (5), and the product of Flux Current 
Ref (63) and stator resistance is stored in IR Voltage Drop (62).
There are three options for autotuning:
•
Static - the motor shaft will not rotate during this test.
•
Dynamic - the motor shaft will rotate during this test.
•
Calculate - tuning data is selected based on the motor nameplate 
data entered.
The static test determines only stator resistance, while the dynamic 
Autotune procedure determines both the stator resistance and 
motor flux current.
IR Voltage Drop (62) is used by the drive to provide additional 
voltage at all frequencies to offset the voltage drop developed 
across the stator resistance. An accurate calculation of the IR 
Voltage Drop will ensure higher starting torque and better 
performance at low speed operation.
If it is not possible or desirable to run the Autotune tests, there are 
two other methods for the drive to determine the IR Voltage Drop 
and Flux Current parameters. One method retrieves the default 
parameters stored in the power EEPROM, and the other method 
calculates them from the user-entered motor nameplate data 
parameters.
If the stator resistance and flux current of the motor are known, you 
can calculate the voltage drop across the stator resistance and 
directly enter these values into the Flux Current and IR Voltage 
Drop parameters.
Refer to the description of the Autotune parameter (61) in chapter 
12 for more information about using this feature.