Wiring Requirements for the Drive

4-5

4.2

Control and Signal Wire

The terminal block on the Main Control board provides terminals for
24VDC power for the eight remote control inputs as well as the
terminals for the analog input/output signals. Refer to tables 4.3 and
4.4 for signal and control wiring specifications.

4.3

Recommended Motor Lead Lengths

Important:

To reduce line disturbances and noise, motor lead
length should not exceed 200 feet for any
non-Reliance Electric motor or any non-inverter duty
motor.

The length of cable between the drive and motor may be limited for
various application reasons. The primary areas of concern are:

Reflected wave

Cable charging

Table 4.3 – Recommended Signal and Control Wire

Signal Type

Wire Type(s)

Description

Minimum

Insulation Rating

Analog I/O

Belden 8760/9460
(or equiv.)

0.750 mm

2

(18 AWG), twisted

pair, 100% shield with drain

1

.

300V, 75-90

°

C

(167-194

°

F)

Belden 8770
(or equiv.)

0.750 mm

2

(18 AWG)

3-conductor, shielded for
remote pot only.

Unshielded
Control

Per US NEC or
applicable national
or local code

-

300V,
60

°

C (140

°

F)

Shielded
Control

Multi-conductor
shielded cable such
as Belden 8770
(or equiv.)

0.750 mm

2

(18 AWG),

3-conductor, shielded.

1

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

Table 4.4 – I/O Terminal Block Specifications

Name

Description

Wire Size Range

1

Torque

Maximum

Minimum

I/O Terminal Block

Signal and control
connections

1.5 mm2
(16 AWG)

0.05 mm2
(30 AWG)

0.5 N-m
(4.4 in-lb)

1

Maximum/minimum that the terminal block will accept. These are not
recommendations.