11-4

SP600 AC Drive User Manual

11.3.1 Accessing Parameters By Group

To access parameters by group, select By Groups from the
Parameters menu on the LCD OIM. Refer to figure 11.2. The LCD
OIM will first display a list of files. Select the file in which the desired
parameter group is located.

Chapter 12 and Appendix E provide the File>Group path for each
parameter.

11.3.2 Accessing Parameters by Number

To access parameters by number, select P Numbers from the
Parameters menu on the LCD OIM. Refer to figure 11.2.

Using this option, you can view the parameters within the selected
access level:

• The Advanced level allows you to view all parameters.

• The Standard level allows you to view a subset of the Advanced

level.

• The Basic level allows you to view a subset of the Standard level.

Note that the LCD OIM will not display any parameter that is not
within the selected access level.

Refer to section 11.3.4 for more information about selecting access
levels.

11.3.3 Accessing Changed Parameters

The Changed Parameters selection provides a method of viewing
only those parameter that are different from the default
configuration. To access the changed parameters, select Changed
Params from the Parameters menu on the LCD OIM. Refer to figure
11.2.