Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 240

Advertising
background image

13-8

SP600 AC Drive User Manual

Table 13.5 – Fault Types

Ty

p

e

Fault Description

Auto-Reset/Run

If the drive is running when this type of fault
occurs, and Auto Rstrt Tries (174) is set to a
value greater than 0, a user-configurable
timer, Auto Rstrt Delay (175) begins. When
the timer reaches zero, the drive attempts to
automatically reset the fault. If the condition
that caused the fault is no longer present, the
fault will be reset and the drive will be
restarted.

Non-Resettable

This type of fault normally requires drive or
motor repair. The cause of the fault must be
corrected before the fault can be cleared. The
fault will be reset on power up after repair.

User-Configurable

These faults can be enabled/disabled to
either annunciate or ignore a fault condition
using Fault Config 1 (238).