Wiring Requirements for the Drive

4-11

Table 4.6 – SP600 400/480 VAC Input Recommended Protection Devices

Model

Number

kW

Dual Element

Time Delay

Fuse

Non-time

Delay Fuse

Circuit

Breaker

1

ND

HD

Min

2

Max

3

Min

2

Max

3

Max

4

400 VAC Input

6SP401-1P1

0.37

0.25

3

3

3

5

15

6SP401-2P1

0.75

0.55

4

6

4

8

15

6SP401-3P4

1.5

1.1

6

6

6

12

15

6SP401-005

2.2

1.5

10

10

10

20

20

6SP401-008

4

3

15

17.5

15

30

30

6SP401-011

5.5

4

15

25

15

45

40

6SP401-014

7.5

5.5

20

30

20

60

60

6SP401-022

11

7.5

30

45

20

80

80

6SP401-027

15

11

40

60

40

120

120

6SP401-034

18.5

15

45

80

45

125

125

6SP401-040

22

18.5

60

90

60

150

150

6SP401-052

30

22

80

125

80

225

240

6SP401-065

37

30

90

150

90

250

280

Model

Number

HP

Dual Element

Time Delay

Fuse

Non-time

Delay Fuse

Circuit

Breaker

1

ND

HD

Min

2

Max

3

Min

2

Max

3

Max

4

480 VAC Input

6SP401-1P1

0.5

0.33

3

3

3

4

15

6SP401-2P1

1

0.75

6

6

3

8

15

6SP401-3P4

2

1.5

6

6

6

12

15

6SP401-005

3

2

10

10

10

20

20

6SP401-008

5

3

15

15

15

30

30

6SP401-011

7.5

5

15

20

15

40

40

6SP401-014

10

7.5

20

30

20

50

50

6SP401-022

15

10

25

45

25

80

80

6SP401-027

20

15

35

60

35

100

100

6SP401-034

25

20

40

70

40

125

125

6SP401-040

30

25

50

90

50

150

150

6SP401-052

40

30

60

110

60

200

200

6SP401-065

50

40

80

125

80

250

250

1

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum

2

Minimum protection device size is the lowest rated device that supplies maximum
protection without nuisance tripping.

3

Maximum protection device size is the highest rated device that supplies drive protection.
For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

4

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.