Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 254
 
13-22
SP600 AC Drive User Manual
Table 13.15 – Drive Will Not Reverse Motor Direction
Indication
Cause(s)
Corrective Action
None
Digital input is not 
selected for reversing 
control.
Check Digital In”x” Sel. 
Choose correct input and 
program for reverse.
Digital input is 
incorrectly wired.
Check input wiring.
Direction Mode (190) 
parameter is 
incorrectly 
programmed.
Reprogram Direction 
Mode (190) for analog 
bipolar or digital unipolar 
control.
Motor wiring is 
improperly phased for 
reverse.
Switch two motor leads.
A bipolar analog 
speed command input 
is incorrectly wired or 
signal is absent.
1. Use meter to check that
an analog input voltage 
is present.
2. Check wiring.
Positive voltage 
commands forward 
direction.
Negative voltage 
commands reverse 
direction.
Table 13.16 – Stopping the Drive Results in a Decel Inhibit Fault
Indication
Cause(s)
Corrective Action
Decel Inhibit fault 
screen.
LCD status line 
indicates Faulted.
The bus regulation 
feature is enabled and 
is halting deceleration 
due to excessive bus 
voltage. Excess bus 
voltage is normally due 
to excessive 
regenerated energy or 
unstable AC line input 
voltages.
Internal timer has halted 
drive operation.
1. Reprogram bus
regulation (parameters 
161 and 162) to 
eliminate any Adjust 
Freq selection.
2. Disable bus regulation
(parameters 161 and 
162) and add a 
dynamic brake.
3. Correct AC input line
instability or add an 
isolation transformer.
4. Reset drive.