Parameter Descriptions

12-71

Enables/disables annunciation of the faults shown in figure 12.41.
See table 13.6 for fault descriptions.

Resets a fault and clears the fault queue.

Enables/disables a fault reset (clear faults) attempt from any source.
This does not apply to fault codes stored in the fault queue, which
are cleared via other actions.

238

Fault Config 1

Range:

See figure12.41

Default:

See figure12.41

Access:

2

Path: Utility>Faults

See also:

Figure 12.41 – Fault Config 1 (238)

1

1

1

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enabled
0 =Disabled
x =Reserved

Bit #

Factory Default Bit Values

UnderV

oltage

Po

w

er Loss

Motor Ov

erLd

Shear Pin

AutRst T

ries

Decel Inhibit

Nibble 1

Nibble 2

Nibble 3

Nibble 4

0

x

x

x

x

0

0

240

Fault Clear

Range:

0 = Ready
1 = Clear Faults
2 = Clr Flt Que

Default:

0 = Ready

Access:

2

Path: Utility>Faults

See also:

241

Fault Clear Mode

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

Access:

2

Path: Utility>Faults

See also: