Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 138

12-8
SP600 AC Drive User Manual
Displays the drive power rating in kilowatts.
Displays the drive input voltage class (208, 240, 400, etc.). This
value will reflect the option selected in parameter 202 (Voltage
Class) and correspond to the connected input voltage.
Displays the drive rated output current. This value corresponds to
the drive nameplate continuous output.
Displays the Main Control board software version.
Set to match the type of motor connected.
26
Rated kW
Range:
0.37 to 15.0 kW [0.1 kW]
Default:
Read Only
Access:
0
Path: Monitor>Drive Data
See also:
32
27
Rated Volts
Range:
208 to 600 V [0.1 VAC]
Default:
Read Only
Access:
0
Path: Monitor>Drive Data
See also:
202
28
Rated Amps
Range:
1.1 to 32.2 Amps [0.1 Amps]
Default:
Read Only
Access:
0
Path: Monitor>Drive Data
See also:
29
Control SW Ver
Range:
0.000 to 65.256 [0.001]
Default:
Read Only
Access:
0
Path: Monitor>Drive Data
See also:
196
40
Motor Type
Range:
0 = Induction
1 = Synchr Reluc
1
2 = Synchr PM
1
Default:
0 = Induction
Access:
2
Path: Motor Control>Motor Data
See also:
1
May conflict with DC Brake feature. See Parameters 157-159. Selection of
1 or 2 requires that paremeter 53 be set to Custom V/Hz = (2).