Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual

Page 138

Advertising
background image

12-8

SP600 AC Drive User Manual

Displays the drive power rating in kilowatts.

Displays the drive input voltage class (208, 240, 400, etc.). This
value will reflect the option selected in parameter 202 (Voltage
Class) and correspond to the connected input voltage.

Displays the drive rated output current. This value corresponds to
the drive nameplate continuous output.

Displays the Main Control board software version.

Set to match the type of motor connected.

26

Rated kW

Range:

0.37 to 15.0 kW [0.1 kW]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

32

27

Rated Volts

Range:

208 to 600 V [0.1 VAC]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

202

28

Rated Amps

Range:

1.1 to 32.2 Amps [0.1 Amps]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

29

Control SW Ver

Range:

0.000 to 65.256 [0.001]

Default:

Read Only

Access:

0

Path: Monitor>Drive Data

See also:

196

40

Motor Type

Range:

0 = Induction
1 = Synchr Reluc

1

2 = Synchr PM

1

Default:

0 = Induction

Access:

2

Path: Motor Control>Motor Data

See also:

1

May conflict with DC Brake feature. See Parameters 157-159. Selection of
1 or 2 requires that paremeter 53 be set to Custom V/Hz = (2).

Advertising