Parameter Descriptions
12-87
361
362
363
364
365
366
Digital In1 Sel - Stop-CF (4)
Digital In2 Sel - Start (5)
Digital In3 Sel - Function Loss (3)
Digital In4 Sel - Jog (10)
Digital In5 Sel - Auto/Manual (18)
Digital In6 Sel - Speed Sel 1 (15)
Range:
0 = Not Used
1 = Enable
2 = Clear Faults
1
3 = Function Loss
4 = Stop - CF
2
5 = Start
6 = Fwd/Reverse
2
7 = Run
3
8 = Run Forward
3
9 = Run Reverse
3
10 = Jog
11 = Jog Forward
12 = Jog Reverse
13 = Stop Mode B
14 = Bus Reg Md B
15 = Speed Sel 1
4
16 = Speed Sel 2
4
17 = Speed Sel 3
4
18 = Manual
19 = Reserved
20 = Acc2 & Dec2
21 = Accel 2
22 = Decel 2
23 = MOP Inc
24 = MOP Dec
25 = OIM Control
26 = PI Enable
27 = PI Hold
28 = PI Reset
29 = Reserved
30 = Reserved
31 = Reserved
32 = Reserved
33 = Reserved
34 = Reserved
35 = Reserved
36 = Reserved
37 = Reserved
38 = Reserved
39 = UserSetBit0
40 = UserSetBit1
Default:
See table 12.6
Access:
361=0
362-366=1
Path: Inputs & Outputs>Digital Inputs
See also:
96, 100, 124, 140, 156, 162, 194, 380