Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 252
 
13-20
SP600 AC Drive User Manual
.
Flashing yellow Ready 
LED.
Enable input is open.
Close terminal block 
enable input.
The terminal block stop 
input is open and control 
source is set to All 
Ports.
Close terminal block stop 
input.
Start inhibit bits are set. Check status in Start
Inhibits (214).
Drive Status 1 (209) 
indicates logic control 
source.
Logic Source Sel (89) is 
not equal to the desired 
OIM (Local OIM, DPI 
Port 2, or DPI Port 3).
Verify setting of Logic 
Source Sel (89). The OIM 
Control digital input 
effectively sets the control 
source to the lowest 
attached OIM port.
Table 13.10 – Drive Does Not Start or Jog From OIM (Continued)
Indication
Cause(s)
Corrective Action
Table 13.11 – Drive Does Not Respond to Changes in Speed Command
Indication
Cause(s)
Corrective Action
LCD OIM Status Line 
indicates “At Speed” 
and output is 0 Hz.
No value is coming from 
the source of the 
command.
1. If the source is an
analog input, check 
wiring and use a meter 
to check for presence 
of signal.
2. Check Commanded
Freq (2) for correct 
source. 
None
Incorrect reference 
source has been 
programmed.
3. Check Speed Ref
Source (213) for the 
source of the speed 
reference. 
4. Reprogram Speed Ref
A Sel (90) for correct 
source.
None
Incorrect reference 
source is being selected 
via remote device or 
digital inputs.
5. Check Drive Status 1
(209), bits 12 - 15 for 
unexpected source 
selections. 
6. Check Dig In Status
(216) to see if inputs 
are selecting an 
alternate source. 
7. Reprogram digital
inputs to correct Speed 
Sel x option.