Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 238
 
13-6
SP600 AC Drive User Manual
DigIn Bad 
Value
Unsupported function selected in Digital In”x” Sel 
parameters (361-366).
Drive OL 
Level 1
The calculated IGBT temperature requires a reduction in 
PWM carrier frequency. If Drive OL Mode (150) is disabled 
and the load is not reduced, an overload fault will eventually 
occur.
Drive OL 
Level 2
The calculated IGBT temperature requires a reduction in 
Current Limit. If Drive OL Mode (150) is disabled and the 
load is not reduced, an overload fault will eventually occur.
Flux Amps 
Ref Rang
Result of autotune procedure (61).
IntDBRes 
OvrHeat
The drive has temporarily disabled the dynamic braking 
regulator because the resistor temperature has exceeded a 
predetermined value.
IR Volts 
Range
The drive autotuning default is Calculate and the value 
calculated for IR Drop Volts is not in the range of 
acceptable values. This alarm should clear when all motor 
nameplate data is properly entered.
MaxFreq 
Conflict
The sum of Maximum Speed (82) and Overspeed Limit (83) 
exceeds Maximum Freq (55). Raise Maximum Freq (55) or 
lower Maximum Speed (82) and/or Overspeed Limit (83) so 
that the sum is less than or equal to Maximum Freq (55).
Motor Type 
Cflct
Motor Type (90) has been set to Sync Prm Mag or Sync 
Reluc, and one or more DC functions (for example, DC 
Boost, DC Brake, etc.) have been activated. DC injection 
functions are incompatible with synchronous motors and 
may demagnetize them.
NP Hz 
Conflict
Fan/pump mode is selected in Torq Perf Mode (53), and the 
ratio of Motor NP Hertz (43) to Maximum Freq (55) is 
greater than 26.
Power 
Loss
Drive has sensed a power line loss.
Prechrg 
Actv
Drive is in the initial DC bus precharge state.
Speed Ref 
Cflct
Speed Ref A Sel (90) or PI Reference Sel (126) is set to 
Reserved.
Under-
Voltage
The bus voltage has dropped below a predetermined value.
Table 13.3 – Alarm Descriptions (Continued)
Alarm
Ty
p
e
Description