Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 141
 
Parameter Descriptions
12-11
Sets the output frequency below which the motor operating current 
is derated. This allows the motor thermal overload to generate a 
fault below rated current. Note that for all settings of overload Hz 
other than 0.0, the overload capacity is reduced to 70% when output 
frequency is zero.
Sets the continuous current operating level for the motor.
The parameter can be used to raise the level of current that will 
cause the motor thermal overload to trip. The effective overload 
factor is a combination of parameters 47 and 48.
Motor FLA x OL Factor = Operating Level (Continuous)
47
Motor OL Hertz
Range:
0.0 to 400.0 Hz
Default:
Motor NP Hz/3
Access:
2
Path: Motor Control>Motor Data
See also:
42, 220
Figure 12.1 – Motor OL Hertz (47)
Changing Overload Hz
20
40
60
80
100
120
0
10
20
30
40
50
60
70
80
90 100
Hertz
Contin
uous Rating
OL Hz = 10
OL Hz = 25
OL Hz = 50
400
48
Motor OL Factor
Range:
0.20 to 2.00 [0.01]
Default:
1.00
Access:
2
Path: Motor Control>Motor Data
See also:
42, 220