7-6

SP600 AC Drive User Manual

Analog Output
Unipolar
0 to +10V Output. Can
Drive a 2k Ohm load
(25 mA short circuit
limit)

Select Source Value:
Param. 342

Adjust Scaling:
Param. 343, 344

2-Wire Control
Non-Reversing
or Reversing with a
Digital Input set to 6

Internal Supply

Disable Digital Input 1:
Param. 361 = 0 “Not Used” or 6

Set Digital Input 2:
Param. 362 = 7 “Run”

2-Wire Control
Reversing

External Supply

Set Digital Input 1:
Param. 361 = 9 “Run Reverse”

Set Digital Input 2:
Param. 362 = 8 “Run Forward”

3-Wire Control

Internal Supply

Use factory default parameter
settings.

3-Wire Control

External Supply

Use factory default parameter
settings.

Digital Output

Form C Relays
Energized in Normal
State.

Select Source:

Param. 380, 384

Table 7.2 – I/O Wiring Examples (Continued)

Input/Output

Connection Example

Required Parameter Settings

+

22

23

2

7

8

9

Stop-Run

+24V

Common

1

2

8

Run Fwd

Run Rev

1

2

7

8

9

Stop

Start

+24V

Common

1

2

8

Stop

Start

11

12

13

24

25

26

Power

Source

or