Pump Tuning

PI Control Tuning (b5 Group)

The built-in PI controller in the iQpump is used to control process variables such as pressure, flow or fluid level. PI control is designed to
eliminate the need for continuous operator attention. The drive has the capability to accept an analog signal 0-10 Vdc or 4-20 mA as
feedback for a PI (Proportional + Integral) control function. A process reference setpoint is connected to the iQpump drive or set via the

digital operator and an actual process value feedback is also brought back to the iQpump drive.

Examples:

Weather the iQpump is used in either Simplex (P1-03 = 0) or Multiplex mode (P1-01 = 1 or 2); the PI settings will need to be adjusted

based on individual system applications. The three parameters below should be the only adjustments required. If control becomes
unstable, please refer to the PI Control (b5-xx) for more details.

Note: These parameters are also programmed through the quick start menu.

Step 1. Make sure that PI is enabled (factory default is enabled b5-01 = 1).

b5-01 PI Mode

The iQpump drive can be used as a stand-alone PI controller. If PI functionality is selected by parameter b5-01, the iQpump drive will
adjust its output to cause the feedback from a transmitter to match the PI Setpoint (b5-19). The setting of b5-01 will determine whether PI

functionality is disabled (b5-01 = “0: Disabled”), enabled (b5-01 = “1: Enabled”).

Step 2. Adjust Proportional Gain Setting.

b5-02 Proportional Gain Setting

Setting Range: 0.00 ~ 25.00

Factory Default: 2.00

The proportional gain will apply a straight multiplier to the calculated difference (error) between the PI Setpoint and the measured

transmitter feedback at terminal A2. A large value will tend to reduce the error but may cause instability (oscillations) if too high. A small
value may allow too much offset between the setpoint and feedback (see

Figure 6.

).

Step 3. Adjust Integral Time

b5-03 Integral Time Setting

Setting Range: 0.0 ~ 360.0 s

Factory Default: 3.0 s

The Integral factor of PI functionality is a time-based gain that can be used to eliminate the error (difference between the setpoint and
feedback at steady state). The smaller the Integral Time set into b5-03, the more aggressive the Integral factor will be. To turn off the
Integral Time, set b5-03 = 0.0 seconds.

Setting

Description

0

Disabled

1

Enabled (

factory default

)

2

Fref + PI