Pump Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual

125

o2 Key Selections

o2-06 Operation Selection when Digital Operator is Disconnected

Leaving o2-06 enabled will cause the iQpump drive to fault, when the digital operator is removed, even if it’s not outputting to the motor.
The reset key on the digital operator will need to be pressed after reconnecting the digital operator to reset the fault and continue normal
operation.

If o2-06 = “0: Disabled” then the iQpump drive will not fault if the digital operator is disconnected, but the iQpump drive will
discontinue motor operation. If full iQpump drive operation is required while the digital operator is removed set o2-06 = “0: Disabled”
and o2-15 = “0: Disabled” (Hand Key Function). If both o2-06 and o2-15 are disabled then the digital operator can be disconnected

without disturbing iQpump drive operation.

o2-07 Cumulative Operating Time Setting

Setting Range: 0 ~ 65535 hours
Factory Default: 0 hours

o2-08 Cumulative Operation Time Selection

The iQpump drive features an Elapsed Timer monitor that records in units of hours. The Elapsed Timer monitor is U1-13. Parameter
o2-08 programs this function to either accumulate elapsed hours based on time the iQpump drive is powered (o2-08 = “0: Power-On Time”)
or time the iQpump drive is running (o2-08 = “1: Running Time”). The iQpump drive is considered “running” anytime there is an active run
command or when the iQpump drive is outputting voltage (i.e. including during deceleration).

Parameter o2-07 allows manual adjustment of the Elapsed Timer, primarily to accommodate maintenance or control board replacement
in the event of damage. To reset the Elapsed Timer back to zero, set o2-07 = 0.

o3 Digital Operator Copy Function

o3-01 Copy Function Selection

Note: The copy function is disabled when serial communication is active.

Setting

Description

0

Disabled

1

Enabled (factory default)

Setting

Description

0

Power-On Time

1

Running Time (factory default)

Setting

Description

0

COPY SELECT (factory default)

1

INV

→ OP READ

2

OP

→ INV WRITE

3

OP

↔ INV VERIFY

-DRIVE-

Elapsed Time

U1-13 = 0H

U1-14 =
U1-15 =

03010
34.1 %