3.3 Drive Mode Indicators

60

YASKAWA TM.iQp.06 iQpump Controller User Manual

3.3

Drive Mode Indicators

The definitions of the iQpump drive mode indicators are shown in

Table 3.2

.

Table 3.2 iQpump Drive Mode Indicators

AUTO Sequence (SEQ) Indicator

The status of the AUTO “Sequence” (SEQ) indicator is shown in

Table 3.3

. This indicator is always “Off” when the iQpump drive is in

the “Hand” mode. When the iQpump drive is in the “Auto” mode, the SEQ indicator status is dependent on the setting of parameter
“b1-02” (Run Command Selection).

Table 3.3 AUTO Sequence (SEQ) Indicator

The status of the AUTO “Reference” (REF) indicator is shown in

Table 3.4

. This indicator is always “Off” when the iQpump drive is in

the “Hand” mode. When the iQpump drive is in the “Auto” mode, the REF indicator status is dependent on the setting of parameter
“b1-01” (Frequency Reference Selection).

Table 3.4 AUTO Reference (REF) Indicator

Run Indicator

The status of the “RUN” indicator is shown in

Table 3.5

when the iQpump drive is in either the “Hand” or “Auto” mode.

Table 3.5 RUN Indicator

Indicator

Definition

FWD

Lit when a forward run command is input and when drive is in “Hand” Mode.

AUTO SEQ

Lit when set up for remote run command. See

Table 3.3

.

AUTO REF

Lit when set up for remote speed command. See

Table 3.4

.

ALARM

Lit when a fault has occurred. Flashes when an alarm has occurred.

Indicator Status

Hand Mode

Auto Mode

On

N/A

Parameter “b1-02” (Run Command Selection) is set to terminal strip, communications, or
an option board as indicated below:

b1-02= 1 (Terminals)

= 2 (Communications)
= 3 (Option PCB)

Off

Parameter “b1-02” (Run Command Selection) is set to digital operator as indicated below:

b1-02 = 0 (Operator)

Indicator Status

Hand Mode

Auto Mode

On

N/A

Parameter “b1-01” (Frequency Reference Selection) is set to terminal strip,
communications, or an option board as indicated below:

b1-01= 1 (Terminals)

= 2 (Communications)
= 3 (Option PCB)

Off

Parameter “b1-01” (Frequency Reference Selection) is set to digital operator as indicated

below:
b1-01= 0 (Operator)

Indicator Status

Condition

On

Drive is running

Blinking

Drive is decelerating to a stop

Off

Drive is stopped