5.2 Pump Basic

128

YASKAWA TM.iQp.06 iQpump Controller User Manual

5.2

Pump Basic

Parameter Overview — P1 Group

Table 5.6

P1 Pump Minimum Speed and No-Flow Detection

The iQpump drive can be programmed to operate the pump motor at a user set minimum speed and has three independent built-in
functions to protect the pump against a no-flow condition.

The following sections describe each of these functions.

Set Minimum Pump Speed (P1-06)

The required minimum operating speed of the pump motor can be set with Parameter P1-06 Minimum Pump Frequency.

Table 5.7

Parameter

No.

Address

Hex

Parameter Name

Digital Operator

Display

Description

Range Default

Menu

Location

P1-01

0600

Pump Mode
Pump Mode

Select type of control operation.
0: Drive Only (Simplex)
1: Drive + 1 Pump
2: Drive + 2 Pumps
3: Memobus network

<0034>

0 ~ 3

0

Programming

P1-02

0601

System Units
System Units

0: WC: InchOfWater
1: psi: lb / SqrInch
2: GPM: Gallons / min
3: F: DegFarenheit
4: CFM: Cubic ft / min
5: CMH: Cubic m / hr
6: LPH: Liters / hr
7: LPS: Liters / s
8: Bar: Bar
9: Pa: Pascals
10: C: DegCelsius
11: Ft: Feet

<0032>

12:%: Percent
13: rpm: Revs / min

<0034>

14: Hz: Hertz

<0034>

0 ~ 14

1

Programming

P1-03

0602

Feedback Device Scaling
Fb Dev Scaling

Scaling of feedback device in user units (P1-02=1, e.g. 150 psi).
Digits 1 through 4 set the maximum feedback number. Digit 5 determines
the number of decimal places.
Digit 5 = 0: Number format is XXXX
Digit 5 = 1: Number format is XXX.X
Digit 5 = 2: Number format is XX.XX
Digit 5 = 3: Number format is X.XXX
Examples:
01000 = 1000
13000 = 300.0
25000 = 50.00
32000 = 2.000

1 ~ 36000

(system

units

P1-02)

00145

Programming

Parameter

No.

Address

Hex

Parameter Name

Digital Operator

Display

Description

Range Default

Menu

Location

P1-06



0605

Minimum Pump
Frequency
Min. Pump Freq.

Minimum drive frequency when operated in the auto mode. Programmed
value will limit minimum PID output. Minimum value has to be
programmed to a value smaller than P3-09 and P3-10 when the drive is
operating in the multiplex mode (P1-01).

0 ~ 120 Hz 40.0 Hz

Pump Quick

Setup



Denotes that parameter can be changed when the drive is running.