6.1 Fault Detection

138

YASKAWA TM.iQp.06 iQpump Controller User Manual

6.1

Fault Detection

When the iQpump drive detects a fault, the fault information is displayed on the digital operator, the fault contact closes, and the motor

coasts to stop. (However, a fault with selectable stopping method will operate according to the stopping method selected.)

• If a fault occurs, take appropriate action according to the table by investigating the cause.
• To restart, reset the fault with any of the following procedures:

• Turn ON the fault reset signal.
• Set “14: Fault Reset” to a multi-function digital input (H1-01 to H1-05).
• Press the RESET key of the digital operator.
• Shut off the iQpump drive input power once, and then turn on again.

Table 6.1 Fault Displays and Processing

WARNING

The Run Command (Start Command) needs to be removed prior to resetting a fault. Resetting a fault by removing and
reapplying power to the iQpump drive while the Run Command is applied, may cause the iQpump drive to start
unexpectedly. Therefore, make sure all personnel are clear from the iQpump drive, motor, and machine prior to resetting
the iQpump drive.

Digital

Operator Display

Description

Cause

Corrective Action

bUS

Option Com Err

Option Communication Error

After initial communication was established, the
connection was lost.

Connection is broken, master has

stopped communicating.

Check all connections, verify all user-

side software configurations.

CE

Memobus Com Err

Modbus Communication Error

Control data was not received correctly for two

seconds.

Connection is broken, master has

stopped communicating.

Check all connections, verify all user-

side software configurations.

CPF00

COM-

ERR(OP&INV)

Operator Communication Fault 1

Transmission between the iQpump and the digital

operator cannot be established within 5 seconds

after supplying power.

Digital operator cable not securely
connected, digital operator

defective, control board defective.

Remove the digital operator once and

then reinstall it.

External RAM of CPU is defective.

Control circuit damage.

Cycle power off and on to the iQpump.
Replace the iQpump.

CPF01

COM-

ERR(OP&INV)

Operator Communication Fault 2

After communication started with the digital

operator, a communication fault occurred for 2

seconds or more.

Digital operator cable not securely

connected, digital operator
defective, control board defective.

Remove the digital operator once and
then reinstall it.
Cycle power off and on to the iQpump.
Replace the iQpump.

CPF02

BB Circuit Err

Baseblock Circuit Fault

Baseblock circuit fault at power-up.

Gate array hardware failure during
power-up.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the control board.

CPF03

EEPROM Error

EEPROM Fault

EEPROM fault, check sum not valid.

Noise or spike on the control
circuit input terminals.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the control board.

CPF04

Internal A/D Err

CPU Internal A/D Converter Fault

Noise or spike on the control
circuit input terminals.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the control board.

CPF05

External A/D Err

CPU External A/D Converter Fault

Noise or spike on the control
circuit input terminals.

Perform a factory initialization.
Cycle power off and on to the iQpump.
Replace the control board.

CPF07

RAM-Err

ASIC Internal RAM Fault
(RAM)

Cycle power off and on to the iQpump.

Control circuit damage.

Replace the iQpump.