D.3 Modbus Data Tables

YASKAWA

TM.iQp.06 iQpump Controller User Manual

221

Monitor Data

The following table shows the monitor data. Monitor data can only be read.

Table D.7 Monitor Data

Register No.

(Hex)

Contents

0020

Drive status

Bit 0

Operation 1: Operating 0: Stopped

Bit 1

Reverse operation 1: Reverse operation 0: Forward operation

Bit 2

Drive startup complete 1: Completed 0: Not completed

Bit 3

Fault 1: Fault

Bit 4

Data setting error 1: Error

Bit 5

Multi-function digital output 1 (terminal M1 - M2) 1: ON 0: OFF

Bit 6

Multi-function digital output 2 (terminal M3 - M4) 1: ON 0: OFF

Bit 7

Not used

Bits 8 to F

Not used

0021

Fault details

Bit 0

Overcurrent (OC) Ground fault (GF)

Bit 1

Main circuit overvoltage (OV)

Bit 2

Drive overload (OL2)

Bit 3

Drive overheat (OH1, OH2)

Bit 4

Not used

Bit 5

Fuse blown (PUF)

Bit 6

PI feedback reference lost (FbL)

Bit 7

External error (EF, EFO)

Bit 8

Hardware error (CPF)

Bit 9

Motor overload (OL1) or overtorque 1 (OL3) detected

Bit A

PG broken wire detected (PGO), Overspeed (OS), Speed deviation (DEV)

Bit B

Main circuit undervoltage (UV) detected

Bit C

Main circuit undervoltage (UV1), control power supply error (UV2), inrush prevention circuit

error (UV3), power loss

Bit D

Missing output phase (LF)

Bit E

Modbus communications error (CE)

Bit F

Operator disconnected (OPR)

0022

Data link status

Bit 0

Writing data

Bit 1

Not used

Bit 2

Not used

Bit 3

Upper and lower limit errors

Bit 4

Data integrity error

Bits 5 to F

Not used

0023

Frequency reference

U1-01

0024

Output frequency

U1-02

0025

Output voltage reference

U1-06

0026

Output current

U1-03

0027

Output power

U1-08

0028

Torque reference

U1-09

0029

Not used

002A

Not used