G.5 Utility Delayed Start Function

YASKAWA

TM.iQp.06 iQpump Controller User Manual

247

G.5

Utility Delayed Start Function

The following is a summary of a set-up procedure and application examples included in this section.

• Utility Delayed Start Function

The Utility Start Delay function allows multiple iQpump drives to be supplied from the same utility source. Using this function, it is
possible to program staggered restart times to eliminate inrush surging on the power source upon restoration of power following a power

outage. This function is used in conjunction with either the HOA keypad or an external run command.

Set-Up Example for the Utility Delayed Start Function

Three 150 HP iQpump drives are connected to the same utility pole. The engineering requires that the drives automatically restart on loss

of power, however the drives must stagger restart by 30 seconds each to eliminate inrush.

Required Parameter Changes:

Note:

All other parameters are at factory default settings.

Related Parameters

Parameter

Drive A

Drive B

Drive C

P4-11

0.5 min

1.0 min

1.5 min

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting Range

Factory

Setting

Menu

Location

P4-11

82A

Utility Start Delay

Utility Delay

Sets the amount of time the drive will delay starting if a run
command is present at power up. A setting of 0.0 disables this
function.

0.0 ~ 1000.0 min

0.2 min

Programming