G.9 iQpump Software Multiplexing Set-up
YASKAWA
TM.iQp.06 iQpump Controller User Manual
257
P9-13
088C
Remove Freq Level
Remove Freq Lvl
When P9-12 = 0 and the output frequency drops below this level for the time set
in P9-15, the lead drive will request to be removed from the system through the
iQpump MEMOBUS network.
When P9-12 = 2 and the output frequency drops below this level and the delta
feedback (feedback - setpoint) has exceeded the level set in P9-14 for the time
set in P9-15, the lead drive will request to be removed from the system through
the iQpump MEMOBUS network.
0.0 ~
120.0 Hz
40.0 Hz Programming
P9-14
088D
Remove Delta Level
Remove Delta Lvl
When P9-12 = 1 and the delta feedback (feedback - setpoint) has exceeded this
level for the time set in P9-15, the lead drive will request to be removed from the
system through the iQpump MEMOBUS network.
When P9-12 = 2 and the delta feedback (feedback - setpoint) has exceeded this
level and the output frequency is below P9-13 for the time set in P9-15, the lead
drive will request to be removed from the system through the iQpump
MEMOBUS network.
0 ~ 6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
P9-15
088E
Remove Delay Time
Remove Dly Time
Delay time before the lead drive is removed from the system.
0 ~
3600 s
10 s
Programming
P9-16
088F
Stabilization Time
Stabilization Time
Time used to stabilize the system when a pump is staged or de-staged. Lead-lag
control and pump protection is suspended during this time.
0 ~
3600 s
3 s
Programming
P9-17
0890
Setpoint Modifier
Set-pt Modifier
System Setpoint is incremented with this value depending on the number of
pumps running.
Pump 1: Setpoint
Pump X: Setpoint + {(X-1) (P9-17)}
-6000.0 ~
6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
P9-18
0891
High Feedback Quick De-
Stage
High FB De-stage
Determines the feedback level to trigger a quick de-stage, set as a percentage of
parameter P1-09. The quick de-stage ignores parameters P9-12 to P9-15 and
only uses an internal 2 second delay.
0.0 ~
100.0%
90.0% Programming
P9-19
0892
Alternation Unit
Alternation Unit
Selects the unit for P9-03
0: Hours (H)
1: Minutes (min)
0 ~ 1
0
Programming
P9-20
0893
Allow Network Run
Allow Net Run
Specifies when a network run command is allowed:
0: Always
1: First / Alternation
2: First Only
3: Alternation Only
0 ~ 3
0
Programming
P9-21
0894
Run Priority
Run Priority
Sets the Lead Drive selection priority overriding the P9-01 selection. If multiple
drives have the lowest P9-21 value, then P9-01 determines which drive becomes
the Lead.
1 ~ 16
8
Programming
P9-22
0895
System Fault Retry
System Flt Retry
Determines the number of times the iQpump MEMOBUS Network will allow
automatic restarts of system faults. The drive uses parameter
L5-03 in determining when to attempt a system fault restart.
For proper operation, this parameter should be set the same for all network
drives.
0 ~ 10
5
Programming
P9-23
0896
Max Number of Running
Pumps
MaxPumps Running
Limits the maximum number of pumps that can run on the system.
1 ~ 16
16
Programming
P9-24
0897
Lead Swap @ Sleep
Lead Swap @ Sleep
When the Lead drive has been asleep for this amount of time and there is another
drive available with a lower P9-21, then this drive will request for a swap.
A setting of 0 disables this function.
0 ~
7200 s
0 s
Programming
P9-25
0898
Highest Node Address
Highest Node Adr
Defines the highest possible node address in the MEMOBUS network. To yield
optimal network performance, it is recommended to set the serial communication
address H5-01 starting from 01h and then consecutively up to the last drive and
then setting this parameter to that H5-01 address.
02 h ~ 10 h
08 h
Programming
P9-26
0899
Master Time-Out
Master Time-0ut
Sets the minimum amount of time that the slave drives will wait for a message
from the master before performing the action set in P9-27.
3.0 ~
10.0 s
4.0 s
Programming
P9-27
089A
Network Recovery
Network Recovery
When no messages are received from the master for the time set in
P9-26, the slave drive will act according to this setting:
0: Automatic - drive will attempt to assume master functionality.
1: Slave/Resume - drive will continue running when the master is lost and will
wait for a master to come on-line.
2: Slave/Stop - drive will stop running when the master is lost and will wait for a
master to come on-line.
3: Fault MSL - fault the drive with an MSL (Master Lost).
0 ~ 3
0
Programming
P9-28
089B
NETSCAN Alarm Time
NETSCAN Alrm Time
Sets the amount of time that the slave drives will wait for a message from the
master before displaying a NETSCAN alarm.
1.0 ~
10.0 s
2.0 s
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location