Parameter List

Table 1 Parameter List

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Initialization

A1-00



0100

Language Selection
Select Language

Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
6: Portugues
*Not returned to factory setting by initialization

0 ~ 6

0

Programming

A1-01



0101

Access Level Selection
Access Level

This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level

0 or 2

2

Programming

90

A1-03

0103

Initialize Parameters
Init Parameters

Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default
values and then parameter o2-03 must be set to “1” to save them. If the
parameter values are changed after o2-03 is set to “1”, the user default
values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial

0 ~ 3330

0

Programming

90

A1-04

0104

Password 1
Enter Password

When the value set into A1-04 does NOT match the value set into A1-
05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters as determined by A1-01 can be changed. Parameter A1-05
can be accessed by pressing the MENU key while holding the RESET
key.

0 ~ 9999

0

Programming

A1-05

0105

Password 2
Select Password

0 ~ 9999

0

Programming



Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.

Sequence

b1-01

0180

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 ~ 3

0

Programming

91

b1-02

0181

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run

<0034>

0 ~ 3, 5

0

Programming

94

b1-03

0182

Stopping Method
Selection
Stopping Method

Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w / Timer (A new run command is ignored if input before the
time in C1-02 expires.)

0 ~ 3

0

Programming

96

b1-07

0186

Local / Remote Run
Selection
LOC/REM RUN Sel

0: Cycle External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the drive will not run.
1: Accept External RUN - If the run command is closed when
switching from hand (local) mode to auto (remote) mode, the drive
WILL run.
Note:

Used with LCD Operator only.

0 ~ 1

0

Programming

b1-08

0187

Run Command Selection
During Program
RUN CMD at PRG

0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when
b1-02 = 0).

0 ~ 1

0

Programming

b1-11

010F

Drive Delay Time Setting
Wait to Run Time

After a run command, drive output will start after this delay time.

0 ~ 600 s

0 s

Programming

DC Braking

b2-01

0189

DC Injection Braking
Start Frequency
DCInj Start Freq

Sets the frequency at which DC injection braking starts when ramp to
stop (b1-03 = 0) is selected. If b2-01 < E1-09, DC injection braking
starts at E1-09.

0.0 ~

10.0 Hz

0.5 Hz

Programming

98