5.2 Pump Basic

130

YASKAWA TM.iQp.06 iQpump Controller User Manual

Figure 5.34

Figure 5.51 Loss of Prime (LOP) Fault

Note: Loss of prime function is only active when the maximum number of pumps defined by P1-01 running at maximum

frequency. Loss of prime function is only active in auto mode.

Fault Display

Description

Cause

Countermeasures

LOP

Loss of Prime

Loss of Prime Fault-
Pump has lost its prime.

If the output current drops below the P1-14 Prime Loss Level for
the time specified in P1-16 and the output frequency is at a high
enough level, a “Loss of Prime” fault occurs
Possible causes:

Dry Well, Air in System, No Water

Allow the system to pump water
again (must have resistance in
pump).

P1-14

Time

OUTPUT

CURRENT

LOSS OF PRIME

(LOP) FAULT

P1-16

<0034>

LOSS OF PRIME TIME

Fmax

– 1Hz

OUTPUT

FREQUENCY