5.3 Pump Protection
134
YASKAWA TM.iQp.06 iQpump Controller User Manual
■
Sleep Function Based on Feedback Level (P2-01 = 2)
The iQpump drive enters sleep mode when feedback signal rises above the level programmed in P2-02 for a time specified in P2-03.
When Pi operation direction (
B5-09 Output Level Selection
) is set for Reverse Output, sleep mode will check for the feedback signal to
fall below P2-02.
Figure 5.36
Figure 5.54 Sleep Function Based on Feedback Level