5.3 Pump Protection

132

YASKAWA TM.iQp.06 iQpump Controller User Manual

Sleep Function Based on Output Frequency (P2-01 = 0)

The iQpump drive enters sleep mode when the output frequency falls below the level programmed in P2-02 for a time specified in P2-03.

Note: In order for the sleep function to be come active the output frequency has the rise above the programmed level P2-02

first or above the Sleep Active Level (P2-20) when programmed to a value greater than 0.0 Hz.

T

Figure 5.52 Sleep Function Based on Output Frequency

Sleep Delay Time

P2-03