Pump Tuning

110

YASKAWA TM.iQp.06 iQpump Controller User Manual

Figure 5.18

Figure 5.6 Custom V/f Pattern Programming Curve

Increasing the voltage in the V/f pattern increases the available motor torque. However, when setting a custom V/f pattern, increase the
voltage gradually while monitoring the motor current, to prevent:

• iQpump drive faults as a result of motor over-excitation

• Motor overheating or excessive vibration

E2 Motor Setup

E2-01 Motor Rated Current

Setting Range: 10 % ~ 200 %

Factory Default: Model Dependent

The Motor Rated Current parameter (E2-01) is necessary information for the iQpump drive motor protection function. The motor
overload protection parameter L1-01 is enabled by default. In addition, motor rated current is used by the torque compensation function

to insure optimum torque production. Set E2-01 to the full load amps (FLA) value stamped on the motor’s nameplate. During Auto-
Tuning, it is required for the operator to enter the motor rated current in parameter T1-04 on the Auto-Tuning menu. If the Auto-Tuning
operation completes successfully, the value entered into T1-04 will be also written into E2-01.

For applications employing a iQpump drive that is oversized for the motor, E2-01 may be set as low as 10 % of the iQpump drive output
current rating. The AMP value in E2-01, however, must always be greater than the “No Load Current” value in parameter E2-03 or an
OPE02 error will be displayed.

E2-03 No Load Current

Setting Range: Model Dependent
Factory Default: Model Dependent

Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper value if the

No Load Current is not stated on the motor nameplate.

E2-04 Number of Motor Poles

Setting Range: 2 ~ 48
Factory Default: 2

This parameter sets the number of motor poles used for no-flow detection function and for the calculation of rpm-related parameters.

Frequency

E1-09 E1-07

E1-06

E1-04

E1-11

Max Voltage E1-05

Mid Voltage B E1-12

Mid Voltage A E1-08

Base Voltage E1-13

Min Voltage E1-10

Min

Freq

Max

Freq

Base

Freq

Mid

Freq

A

Mid

Freq B

Freq A