B.3 Capacity Related Parameter Values

YASKAWA

TM.iQp.06 iQpump Controller User Manual

207

Table B.4 480 Vac iQpump Drives

Drive Model

CIMR-P7U‰-107

Nominal

Hp

Factory

Default

for

b8-04

Factory

Default

for

E2-01

Factory

Default

for

E2-03

Factory

Default

for

E2-05

Factory

Default

for

L2-02

Factory

Default

for

L2-03

Factory

Default

for

L2-04

Factory

Default

for

L8-02

Factory

Default

for

L8-06

40P4

0.5 / 0.75

576.40

1.0

0.6

38.198

0.1

0.1

0.3

95

°C

5

40P7

1

447.40

1.6

0.8

22.459

0.1

0.2

0.3

95

°C

7.5

41P5

1.5 / 2

338.80

3.1

1.4

10.100

0.2

0.3

0.3

95

°C

10

42P2

3

313.60

4.2

1.5

6.495

0.3

0.4

0.3

90

°C

10

43P7

5

245.80

7.0

2.3

3.333

0.5

0.5

0.3

95

°C

12

45P5

7.5

189.50

13.3

2.6

1.595

1.0

0.6

0.3

95

°C

10

47P5

10

145.38

19.9

4.0

1.152

1.0

0.7

0.3

90

°C

20

49P0

15

145.46

21.0

5.6

0.922

2.0

0.8

0.3

95

°C

23

4011

20

140.88

26.5

5.6

0.922

2.0

0.8

0.3

95

°C

23

4015

25

126.26

32.9

7.6

0.550

2.0

0.9

0.3

95

°C

17

4018

30

115.74

52.3

7.8

0.403

2.0

1.0

0.6

98

°C

17

4024

40

89.08

52.0

8.6

0.269

2.0

1.1

0.6

85

°C

20

4030

50

92.54

65.6

10.9

0.269

2.0

1.1

0.6

85

°C

20

4037

60

76.32

79.7

19.1

0.155

2.0

1.1

0.6

85

°C

20

4045

75

71.56

95.0

22.0

0.122

2.0

1.2

0.6

90

°C

20

4055

100

67.20

130.0

24.0

0.088

2.0

1.2

1.0

90

°C

20

4075

125

46.20

130.0

36.0

0.092

2.0

1.3

1.0

98

°C

16

4090

150

38.91

156.0

40.0

0.056

2.0

1.5

1.0

108

°C

16

4110

200

36.23

190.0

49.0

0.046

2.0

1.7

1.0

100

°C

16

4160

250

30.13

270.0

70.0

0.029

2.0

1.8

1.0

108

°C

14

4185

300 / 350

30.57

310.0

81.0

0.025

2.0

0.7

1.0

95

°C

15

4220

400 / 450

27.13

370.0

96.0

0.020

2.0

0.8

1.0

100

°C

15

4300

500+

21.76

500.0

130.0

0.014

2.1

0.9

1.0

95

°C

15

Note:

b8-04 = Energy Savings Coefficient
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level