2.3 Control Wiring

52

YASKAWA TM.iQp.06 iQpump Controller User Manual

Control Circuit Wiring Precautions

Observe the following precautions when wiring control circuits:

1. Separate control wiring from power/motor wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, ,

1,

2, and

3) and other

high-power lines.

2. Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, and M4 (digital outputs) from wiring to other control circuit

terminals.

3. If using an optional external power supply, ensure it is a UL Listed Class 2 power supply source.
4. Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults. Prepare cable ends as shown in

Figure 2.7.

5. Connect the shield wire to terminal E (G).
6. Insulate the shield with tape to prevent contact with other signal lines and equipment.

Figure 2.7 Preparing the Termination of Shielded Twisted-pair Cables

Shield sheath

Insulation

Connect to shield sheath

terminal E(G) at drive

Insulate with tape

Do not connect here.