5.1 iQpump Drive Basic Programming Parameters

YASKAWA TM.iQp.06 iQpump Controller User Manual

91

Important: Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The following parameters will not be reset
when parameter A1-03 = 2220 or 3330:

• A1-00, Language Selection
• E1-03, V/f Pattern Selection
• o2-04, kVA Selection

b1 Sequence

The Sequence Group contains parameters associated with starting and stopping the iQpump drive. Parameters involving the Run
Command, Speed Reference and Setpoint location, Stopping Method and Hand / Auto changeover are located in this group.

b1-01 Frequency Reference Selection

In order to run the iQpump drive and motor, the iQpump drive must receive a Run command and a Auto Setpoint command. Parameter

b1-01 specifies from where the Auto setpoint is received when in the “Auto” mode. Switching into the “Auto” mode can be done by
pressing the AUTO button on the digital operator while the iQpump drive is stopped.

Important: If a Run command is input to the iQpump drive but no corresponding Auto setpoint is input, the Run indicator on the digital

operator will turn on and the STOP indicator on the digital operator will blink.

If the iQpump drive should follow the “Hand Reference” set by the digital operator: Use the “Hand” mode by pressing the hand key
and set P5-01 = “1: Hand Reference (P5-02).” The hand reference can then be entered into the U1-01 monitor parameter in the “-DRIVE-

” Menu.

The iQpump drive offers the ability to provide four types of “Auto Setpoint” reference sources. These Auto Setpoint reference sources
are determined by the setting of b1-01 and the drive set to “Auto” mode by pressing the Auto key on the digital operation.

Note: Prior to programming, it is recommended to first select the system units (P1-02) and the feedback device, Scaling (P1-

03). P1-03 will automatically scale the iQpump setpoint.
Example:
P1-02 = 1: psi
P1-03 = 200, feedback range = 200 psi.

If the iQpump drive should follow an “Auto Set-Point” set by the digital operator: Set b1-01 = “0: Operator” (factory default), The

Auto setpoint can then be entered into the U1-01 monitor parameter in the “-DRIVE-” menu.

Setting

Description

0

Operator - Digital Preset Speed d1-01 (factory default)

1

Terminals - Analog Input Terminal A1 (or Terminal A2, see Parameter H3-13)

2

Serial Com - RS-485 Terminals R+, R-, S+ and S-

3

Option PCB - Option Board connected at 2CN