480 vac, C.1 standard iqpump drive specifications, Yaskawa – Yaskawa iQpump Controller User Manual User Manual

Page 211

Advertising
background image

C.1 Standard iQpump Drive Specifications

YASKAWA

TM.iQp.06 iQpump Controller User Manual

211

480 Vac

Table C.2 480 Vac iQpump Drive Specifications

Table C.2 480 Vac iQpump Drive Specifications (Continued)

Model Number CIMR-P7U‰-107

40P4

40P7

41P5

42P2

43P7

45P5

47P5

49P0

4011

4015

4018

Ou

tp

u

t

Ra

ti

n

g

s

Rated output capacity (kVA)

1.4

1.6

2.8

4.0

5.8

9.5

13.0

16.0

21.0

26.0

30.0

Motor HP (460V)

0.5 / 0.75

1

1.5/2

3

5

7.5

10

15

20

25

30

Rated output current (A)

1.8

2.1

3.7

5.3

7.6

12.5

17.0

21.0

27.0

34.0

40.0

Max. output voltage (V)

3-phase; 380, 400, 415, 440, 460, or 480 Vac (Proportional to input voltage.)

Max. output frequency (Hz)

120 Hz

Po

w

er Su

pp

ly

C

h

ar

act

er

ist

ics

Rated voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460 or 480 Vac, 50/60 Hz

Rated input current (A)

2.2

2.5

4.4

6.4

9.0

15

20

26

33

40

48

Allowable voltage fluctuation

+ 10 %, - 15 %

Allowable frequency fluctuation

±5 %

Co

n

tr

o

l

C

h

ar

ac

te

ri

s

tic

s

Measures for
power supply
harmonics

DC Reactor

Optional

12-pulse
Rectification

Not Possible

Model Number CIMR-P7U‰-107

4024

4030

4037

4045

4055

4075

4090

4110

4160

4185

4220

4300

Ou

tp

u

t

Ra

ti

n

g

s

Rated output capacity (kVA)

40.0

51.0

59.0

73.0

95.0

120.0

140.0

180.0

230.0

315.0

390.0

510.0

Motor HP (460V)

40

50

60

75

100

125

150

200

250

300 / 350

400 / 450

500+

Rated output current (A)

52.0

67.2

77.0

96.0

125.0

156.0

180.0

240.0

304.0

414.0

515.0

675.0

Max. output voltage (V)

3-phase, 380, 400, 415, 440, 460 or 480 Vac (Proportional to input voltage)

Max. output frequency (Hz)

120 Hz

P

o

we

r S

u

p

p

ly

C

h

ar

ac

te

ri

st

ic

s

Max. voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460, or 480 Vac, 50/60 Hz

Rated input current (A)

57

74

85

106

134

172

198

264

334

456

567

743

Allowable voltage fluctuation

+ 10 %, - 15 %

Allowable frequency fluctuation

±5 %

Co

n

tr

o

l

C

h

ar

ac

te

ri

s

tic

s

Measures for power
supply harmonics

DC Reactor

Built-in

12-Pulse
Rectification

Possible

Note:

The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and drive, be sure that the drive's rated output current is
applicable for the motor's rated current.
A 3-wire phase-shifting transformer is required on the power supply for 12-pulse rectification.

Advertising