5.1 iQpump Drive Basic Programming Parameters

90

YASKAWA TM.iQp.06 iQpump Controller User Manual

5.1

iQpump Drive Basic Programming Parameters

The initialization group contains parameters associated with initial set-up of the iQpump drive. Parameters involving the display

language, access levels, initialization and password are located in this group.

A1 Initialization

A1-01 Access Level Selection

If the iQpump drive is programmed for Operation Only (A1-01 = “0: Operation Only”), then only the Operation and Programming menus

are accessible. Within the Programming menu, only parameters A1-01 and A1-04 are adjustable.

If A1-01 is configured for Advanced Access (A1-01 = “2: Advanced Level”), then all menus and all parameters are shown. If the Access
Level Selection is set to Advanced, all parameters should be adjustable unless:

1. The iQpump drive parameters are password protected (A1-04), preventing access to A1-00 through A1-03 and all A2 parameters.
2. A digital input configured as a Program Lockout (H1-0x = 1B) is active.
3. During serial communication writing, if a parameter change is also attempted via the digital operator, a “BUSY - WRITE

PROTECTED” message will display. Parameter change will not be possible from the digital operator until an Enter command is

received via the serial communication to finish the serial writing process.

A1-03 Initialize Parameters

The iQpump drive can be set to one of three default states via parameter A1-0.

1. User Initialization – 1110: The modified iQpump drive parameters are returned to the values selected as user settings. User settings are

stored when parameter o2-03 = “1: Set Defaults.”

1. 2-Wire Initialization – 2220: The iQpump drive parameters are returned to factory default values with digital inputs S1and S2

configured as Forward Run and Reverse Run, respectively.

1. 3-Wire Initialization – 3330: The iQpump drive parameters are returned to factory default values with digital inputs S1, S2, and S5

configured as Run, Stop, and Forward / Reverse respectively.

After an initialization is performed, parameter A1-03 will automatically reset to 0.

Figure 5.1

Figure 5.1 2 & 3-Wire Control Wiring Examples

Setting

Description

0

Operation Only

2

Advanced Level (factory default)

Setting

Description

0

No Initialize (factory default)

1110

User Initialize

2220

2-Wire Initialize

3330

3-Wire Initialize

S1

S2

SN

FWD Run/Stop

REV Run/Stop

2-wire control

3-wire control

2-wire control

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command
(run on momentary close)
Stop command
(stop on momentary open)

Sequence input common

SN