2.2 Wiring Main Circuit Terminals

YASKAWA TM.iQp.06 iQpump Controller User Manual

45

Cable Length Between iQpump Drive and Motor

The iQpump drive should be installed as close as possible to the motor to minimize the length of load side power cable needed between
the iQpump drive and the motor.

If the cable between the iQpump drive and the motor is too long, drive output current will increase as the leakage current from the cable

increases, which may affect peripheral devices. Reduce the cable length whenever possible, or adjust the carrier frequency (set in C6-02)
as shown in

Table 2.6

to prevent problems with peripheral devices.

Run the line-side power cables, load-side power cables and the control wiring in a separate conduit. Careful attention to this

recommended design practice will avoid many potential motor and iQpump drive-related problems.

Table 2.6 Motor Cable Length vs. Carrier Frequency (C6-02)

(See the limitations on carrier frequency, based on iQpump drive capacity and model number in

Appendix B

).

Ground Wiring

Observe the following precautions when connecting the ground wire:

1. 208-240 Vac iQpump drives should have a ground connection with resistance of less than 100

Ω.

2. 480 Vac iQpump drives should have a ground connection with resistance of less than 10

Ω.

3. Do not share the ground wire with other devices, such as motors or large-current electrical equipment.

4. Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire.

Leakage current flows through the iQpump drive. Therefore, if the distance between the ground rod and the ground terminal is too

long, potential on the ground terminal of the iQpump drive will become unstable.

5. When using more than one iQpump drive, be careful not to loop the ground wire. See

Figure 2.2

.

Figure 2.2 Ground Wiring Examples

Control Circuit Ground Terminals

The removable iQpump drive control terminal card provides two ground terminals (marked TB3 and TB4) to accept the control wire

shield connection. The control wire shield should be connected on this end only, the opposite end should be isolated with electrical tape.

Motor Cable Length

328ft. (100m) maximum

More than 328ft. (100m)

Carrier Frequency

8 kHz maximum

2 kHz maximum

IMPORTANT

• Grounding of the iQpump enclosure and motor is required for proper system operation.

NO

OK

OK

NOT OK