2.3 Control Wiring

YASKAWA TM.iQp.06 iQpump Controller User Manual

55

Feedback Device (3-Wire)

Connection of a 3-Wire 0 ~ 10 Vdc Feedback Device (H3-08 = 0)

In order to use a 4 ~ 20 mA feedback device, parameter H3-08 Terminal A2 Signal has to be programmed to 2.

Note: In order to use a 0 ~ 10V feedback device parameter for terminal A2, the parameter H3-08 Terminal A2 Signal has to be

programmed to 0 and DIP Switch S1-2 has to be set to OFF for the iQpump to accept a 0 ~ 10 Vdc signal.

Figure 2.12 Feedback Device (3-Wire) Connection