4.2 iQpump Drive Quick Start-Up Procedures

YASKAWA TM.iQp.06 iQpump Controller User Manual

87

Feedback Signal Check

Verify the feedback signal level the drive keypad display matches the mechanical pressure gauge.

Refer to parameters P1-02 and P1-03, if the feedback device scaling or system units are incorrect.

Step # 7 - Auto Mode Operation

The iQpump drive can be operated in automatic mode when the following actions are performed:
• All parameters are programmed
• Pump motor direction is verified
• Feedback signal is verified

At this point, the digital operator should display as shown in

Figure 4.13

.

Figure 4.13 Digital Operator

Set System Setpoint

FEEDBACK SIGNAL LEVEL

FWD LED

ON

01 Flashing

RUN LED OFF

STOP LED ON

Next, press

to access or modify the system set -point that was entered using

Use

to select the digit and

to change the system set -point.

Next press

Next, press the

AUTO

button to start the
iQpump.

to store set -point and press

operation menu.

to return to the main

parameter d1-01 System Set-point in the Pump Quick Setup Menu

Example: 80 PSI