Step # 7 - auto mode operation, Feedback signal check, Set system setpoint – Yaskawa iQpump Controller User Manual User Manual
Page 87

4.2 iQpump Drive Quick Start-Up Procedures
YASKAWA TM.iQp.06 iQpump Controller User Manual
87
■
Feedback Signal Check
Verify the feedback signal level the drive keypad display matches the mechanical pressure gauge.
Refer to parameters P1-02 and P1-03, if the feedback device scaling or system units are incorrect.
◆ Step # 7 - Auto Mode Operation
The iQpump drive can be operated in automatic mode when the following actions are performed:
• All parameters are programmed
• Pump motor direction is verified
• Feedback signal is verified
At this point, the digital operator should display as shown in
.
Figure 4.13 Digital Operator
■
Set System Setpoint
FEEDBACK SIGNAL LEVEL
FWD LED
ON
01 Flashing
RUN LED OFF
STOP LED ON
Next, press
to access or modify the system set -point that was entered using
Use
to select the digit and
to change the system set -point.
Next press
Next, press the
AUTO
button to start the
iQpump.
to store set -point and press
operation menu.
to return to the main
parameter d1-01 System Set-point in the Pump Quick Setup Menu
Example: 80 PSI