Warning – Yaskawa iQpump Controller User Manual User Manual

Page 142

Advertising
background image

6.1 Fault Detection

142

YASKAWA TM.iQp.06 iQpump Controller User Manual

Uv2

CTL PS Undervolt

Control Power Supply Undervoltage

Undervoltage of the control circuit when running.

External load connected pulling

down the iQpump power supplies.

Cycle power off and on to the iQpump.
Repair or replace the Power PCB / Gate

iQpump PCB.
Remove all control wiring and test

iQpump.

Uv3

MC Answerback

Soft Charge Circuit Fault

The pre-charge contactor opened while the

iQpump was running.

Contacts on the soft charge

contactor are dirty and the soft
charge contactor does not function

mechanically.

Cycle power off and on to the iQpump.
Check the condition of the soft charge

contactor.
Repair or replace the Power PCB / Gate
iQpump PCB.

WARNING

Some features within the PI function group cause the iQpump to shut down momentarily (e.g. Sleep Function, Snooze
Function, Feedback Loss feature etc.) Upon recovery from the conditions that activate these features, the iQpump may
start unexpectedly. Therefore, when enabling these features take appropriate measures to notify personnel working with
this equipment that unexpected starting may occur.

Digital

Operator Display

Description

Cause

Corrective Action

Advertising