If the Sleep Boost pressure does not achieve 110 psi before shutting down:

• Ensure that the pump system in use can produce this Sleep Boost psi level.
• Extend the Sleep Boost Time (P2-22) in increments of 5 s. With longer acceleration rates, the Sleep Boost Time may require

adjustment.

• The drive will stop the Sleep Boost Cycle when either the boost pressure of 110 psi is achieved and/or when the Sleep Boost Time has

expired.

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P2-21

820

Sleep Boost Level
Sleep Boost Lvl

This parameter sets the amount of boost applied to the setpoint just
before going to sleep. A setting of 0.0 disables the Sleep Boost
function. (Internally limited to 25% of P1-03)

0.0 ~

6000.0

(system

units

P1-02)

0.0

Programming

P2-22

821

Sleep Boost Maximum Time
Sleep Boost Time

This parameter sets the amount of time the system (feedback) has to
reach the “boosted” setpoint. If more than this time elapses, the drive
will go to sleep.

1.0 ~

160.0 s

5.0 s

Programming