Troubleshooting – Yaskawa iQpump Controller User Manual User Manual
Page 246

246
YASKAWA
TM.iQp.06 iQpump Controller User Manual
G.4 Sleep/Sleep Boost Function
Table G.3 Related Parameters
<0034>
◆ Troubleshooting
If the Sleep Boost pressure does not achieve 110 psi before shutting down:
• Ensure that the pump system in use can produce this Sleep Boost psi level.
• Extend the Sleep Boost Time (P2-22) in increments of 5 s. With longer acceleration rates, the Sleep Boost Time may require
adjustment.
• The drive will stop the Sleep Boost Cycle when either the boost pressure of 110 psi is achieved and/or when the Sleep Boost Time has
expired.
Parameter
No.
Addr. Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
P2-21
820
Sleep Boost Level
Sleep Boost Lvl
This parameter sets the amount of boost applied to the setpoint just
before going to sleep. A setting of 0.0 disables the Sleep Boost
function. (Internally limited to 25% of P1-03)
0.0 ~
6000.0
(system
units
P1-02)
0.0
Programming
P2-22
821
Sleep Boost Maximum Time
Sleep Boost Time
This parameter sets the amount of time the system (feedback) has to
reach the “boosted” setpoint. If more than this time elapses, the drive
will go to sleep.
1.0 ~
160.0 s
5.0 s
Programming