Figure 4.1, Step # 2 - connect pump motor and line power – Yaskawa iQpump Controller User Manual User Manual

Page 78

Advertising
background image

4.2 iQpump Drive Quick Start-Up Procedures

78

YASKAWA TM.iQp.06 iQpump Controller User Manual

Cover Removal for Models CIMR-P7U2022 through 2110 (30 HP to 150 HP @ 208 V / 240V ) and 4030 through 4300 (40 HP

to 500 HP @ 480 V)

Loosen the screws on the left and right at the top of the terminal cover, pull down the terminal cover in the direction of arrow 1 and then

lift up on the terminal cover in the direction of arrow 2. Refer to

Figure 4.2

.

Figure 4.1

Attaching the Terminal Cover

After wiring the terminal block, attach the terminal cover by reversing the removal procedure.

Attaching the Terminal Cover for Models CIMR-P7U2018 / 4018-107 and Smaller

insert the tab on the top of the terminal cover into the groove on the iQpump drive and press in on the bottom of the terminal cover until
it snaps into place.

Attaching the Terminal Cover for iQpump drives CIMR-P7U2022 / 4030-107 and Larger

Insert the tab on the top of the terminal cover into the groove on the iQpump drive, and secure the terminal cover by lifting it up toward

the top of the iQpump drive.

Step # 2 - Connect Pump Motor and Line Power

Figure 4.3

and

Figure 4.4

illustrate the electrical connections for the input power and motor terminals for various iQpump models. Select

the proper diagram for the model you are installing (see Step 1). WITH POWER OFF make the appropriate connections.

Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is grounded properly as shown.

Figure 4.1 Removing the Terminal Cover

Figure 4.2 Removing the Terminal Cover

DANGER

LETHAL VOLTAGES ARE PRESENT - Before applying power to the iQpump, ensure that the terminal cover is
fastened and all wiring connections are secure. After the power has been turned OFF, wait at least five minutes until the
charge indicator extinguishes completely before touching any wiring, circuit boards or components. Failure to comply
will result in death or serious injury by electrocution.

NOTICE

DO NOT CONNECT ANY OF THE FOLLOWING TERMINALS TO EARTH GROUND.
Damage to the drive will occur.

1

2

B1

B2

-

+

+1

+2

Advertising