E.1 Branch Circuit Short Circuit Protection

E.1

Branch Circuit Short Circuit Protection

The following fuses and/or circuit breakers may be required between the AC power supply and the iQpump drive input terminals L1(R),

L2(S), and L3(T) depending on local electrical codes. Use Table E.1 or E.2 when selecting fuses and circuit breakers to comply with NEC
codes. Select one of the fuses in Table E.3 or E.4 when selecting semiconductor fuses to provide iQpump drive input I

2

t protection and

comply with UL, CSA, NEC, and CEC branch circuit short circuit protection requirements.

Table E.1 Recommended Fuse and Circuit Breaker Ratings per NEC (208-240 Vac Input)

Fuse Type:

UL designated Time-Delay or Non-Time-Delay Fuse
Class: CC, J, T, RK1 or RK5
Designators (typical): KTK, FNQ, FRS, LPJ, LPS, JKS, JJN, or JJS
Voltage Rating: 250 V for drives with 208-240 V input

600 V for drives with 480 V input

Circuit Breaker Type:

Inverse Time (MCCB) or Instantaneous Trip (MCP)
Voltage Rating: 600 V

Model

CIMR-P7U‰-107

HP

Input

Amps

*1

(Continuous

Rating)

Output

Amps

*1

(Continuous

Rating)

Fuse

Selection Criteria

Circuit Breaker

Selection Criteria

Maximum

Time-Delay

Fuse Rating (A)

Maximum Non-Time-

Delay Fuse Rating (A)

Maximum CB

Rating (A)

20P4

0.5/0.75

4.3

3.6

6

12

15

20P7

1

5.5

4.6

8

12

15

21P5

1.5/2

9.4

7.8

15

15

15

22P2

3

13

10.8

20

20

20

23P7

5

20

16.8

30

30

35

25P5

7.5

24

23

40

50

45

27P5

10

37

31

60

80

80

2011

15

53

46.2

80

80

100

2015

20

70

59.4

110

125

125

2018

25

89

74.8

125

150

150

2022

30

98

88

150

150

175

2030

40

120

115

200

200

225

2037

50

180

162

250

250

300

2045

60

212

192

300

300

350

2055

75

237

215

350

350

450

2075

75/100

350

312

450

450

600

2090

125

396

360

600

600

700

2110

150

457

415

700

700

900

*1 Input and Output Amps are based on the Normal Duty (ND) current rating. Consult the Specification section for details on the Heavy Duty (HD) and Normal Duty (ND) ratings.